Outdoor High Voltage Vacuum Circuit Breaker

ZW32-24 outdoor HV vacuum circuit breaker

Update: 2020/5/8      View:
  • Brand:    
  • Type:    ZW32-24
  • Order Online
Introduction

ZW32-24 Outdoor High Voltage Vacuum Circuit Breaker

Summary
ZW32-24 outdaoor HV vacuum circuit breaker is a 3-phase AC 50Hz 24kV outdoor switch equipment.
♦ Installation way: pole mounted;
♦ Operating mechanism: spring operating mechanism and permanent magnetic operating mechanism;
♦ Pole type: integrated pole;
♦ Application: outdoor 24kV substation, power plant.
♦ Operation type: manual, electric, remote control.

※ Product Standards
♦ IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Specification of High-voltage AC Circuit-breakers
 
※ Environmental Conditions
♦ Ambient temperature: -35°C ~ +40°C;
♦ Altitude: ≤2000m;
♦ Wind speed ≤ 35m/s;
♦ Earthquake intensity: ≤8 level;
♦ Filthy level: IV;
♦ Installation places: No fire, explosion hazard or serious filthy.

Technical Specifications

No. Item Units Parameters
1 Rated voltage Kv 24
2 Rated frequency Hz 50
3 Rated current A 630 1250
4 Rated short-circuit breaking current kA 20 25
5 Rated peak withstand current(peak) kA 50 63
6 Rated short-circuit closing current(peak) kA 40 63
7 Rated short-time withstand current and duration kA/S 20/4 25/4
8 Rated operation sequence O-0 . 3s-CO-180s-CO
9 Mechanical life Times 10000
10 Breaking times of  rated short-circuit breaking current Times 20
11 1min power frequency withstand voltage (wet) over the groundlinter phase/fracture kV 50/65
(dry) over the groundlinter phaseffracture 65/79
Secondary loop 3
12 Lighting impulse withstand voltage(peak)  Overthe group,interphase/fracture KA 125/145

Model Implication


Overall Dimensions